Free download

The I/O list template

One signal per row, the columns a loop check needs and nothing it does not: tag, description, type and medium, where the signal lands on the controller, the electrical span and the engineering range kept apart, the fail-safe state, the device. Dropdowns on the type, the medium and the fail-safe state, four example rows to overwrite, a second sheet that explains every column. No account needed.

Download the template (.xlsx)Excel 2016 or later, LibreOffice, Google Sheets.

Step 1

Fill it

Keep the header row. Overwrite the grey examples. Digital signals have no range; analogue ones carry 0–2 bar g, and 4–20 mA too when they are hardwired. Say in Medium whether the signal is hardwired, on a bus or virtual.

Step 2

Import it

In MGTrace, open the project's I/O List document and click Import…: new tags are added with their pending loop check, existing tags are updated or skipped — your choice.

Step 3

Generate the loop checks

Pick the signals and generate their loop tests from the templates per class — type and medium — each with its own range and unit, into the loop-check protocol — executed and signed there.

What is in it

Columns marked * are required to import; leave the rest empty when they do not apply. The importer also accepts a .csv with the same headers, and understands common spellings (Signal tag, Manufacturer, Remarks…).

ColumnExampleWhat goes in it
Tag *PT-101The signal's tag as on the P&ID and the I/O list (one per row, unique in the project).
Description *Headspace pressureWhat the signal is: the instrument or actuator and its service.
Type *AIDI, DO, AI or AO: what the signal is and how it is tested (two states, or points along a span). Bus and virtual signals use the same four types; the Medium column says how they arrive.
MediumHardwiredHardwired (a cable to the card; tested at the terminals), Bus (Profinet, IO-Link, Modbus…; tested at the device) or Virtual (computed by the controller; tested on the HMI). Empty = Hardwired.
Field tag—Only when the tag marked in the field differs from the I/O tag.
Rack0Controller rack / chassis.
Slot3Card slot.
Channel0Channel on the card.
PLC address%IW64The address as the PLC writes it (%IW64, I:1/3…), or the device's bus address.
Signal4-20 mAThe electrical signal or protocol: 4-20 mA, 24 VDC, NAMUR, Profinet…
Signal low4Hardwired analogue only: low end of the electrical span (4).
Signal high20Hardwired analogue only: high end of the electrical span (20).
Signal unitmAmA, V…
Range low0Analogue (any medium): engineering range low (0).
Range high2Engineering range high (2).
Engineering unitbar gbar g, °C, L/min… as shown on the HMI.
Fail-safe stateFail lowDigital: De-energized, Energized, Fail open, Fail closed, Fail last state. Analogue: Fail low, Fail high, Fail last value.
Device brandEndress+HauserInstrument or actuator manufacturer (optional).
Device modelCerabar PMP51Model (optional). Brand and model together make one catalogue entry.
Serial number—Serial of the installed unit (optional).
NotesHeadspace, top nozzleAnything else: location, cable, remarks.

Type and medium

The type says what the signal is and how it is tested: two states, or points along a span.

DI
Digital input — a contact, a proximity switch, a level switch.
DO
Digital output — a valve solenoid, a motor start, a lamp.
AI
Analogue input — a transmitter: 4–20 mA, 0–10 V, Pt100.
AO
Analogue output — a control valve positioner, a drive speed reference.

The medium says how it reaches the controller and so where it is tested. Together they make the class MGTrace shows: AI for a hardwired analogue input, NAI for the same value over a bus, VDI for a calculated flag.

Hardwired
A cable to the card. Tested at the terminals with a calibrator or a multimeter.
Bus
Profinet, IO-Link, Modbus, Ethernet/IP… Tested at the device, or by forcing it there.
Virtual
Computed by the controller. Tested on the HMI from the inputs that feed it.

Two ranges, not one

A pressure transmitter sends 4–20 mA and means 0–2 bar g. The loop check injects the first and reads the second, at 0, 50 and 100 % of span — so the template keeps Signal low / high / unit apart from Range low / high / Engineering unit. A list that mixes them is the usual reason a loop check is "done" and the HMI still reads wrong.

From the list to signed loop checks

Import the filled template into a project, trace each signal to the design element that specifies it, generate the loop checks per signal, execute them from a phone in the cabinet room and sign. Free for the first users, no time limit.