Free download
The I/O list template
One signal per row, the columns a loop check needs and nothing it does not: tag, description, type and medium, where the signal lands on the controller, the electrical span and the engineering range kept apart, the fail-safe state, the device. Dropdowns on the type, the medium and the fail-safe state, four example rows to overwrite, a second sheet that explains every column. No account needed.
Step 1
Fill it
Keep the header row. Overwrite the grey examples. Digital signals have no range; analogue ones carry 0–2 bar g, and 4–20 mA too when they are hardwired. Say in Medium whether the signal is hardwired, on a bus or virtual.
Step 2
Import it
In MGTrace, open the project's I/O List document and click Import…: new tags are added with their pending loop check, existing tags are updated or skipped — your choice.
Step 3
Generate the loop checks
Pick the signals and generate their loop tests from the templates per class — type and medium — each with its own range and unit, into the loop-check protocol — executed and signed there.
What is in it
Columns marked * are required to import; leave the rest empty when they do not apply. The importer also accepts a .csv with the same headers, and understands common spellings (Signal tag, Manufacturer, Remarks…).
| Column | Example | What goes in it |
|---|---|---|
| Tag * | PT-101 | The signal's tag as on the P&ID and the I/O list (one per row, unique in the project). |
| Description * | Headspace pressure | What the signal is: the instrument or actuator and its service. |
| Type * | AI | DI, DO, AI or AO: what the signal is and how it is tested (two states, or points along a span). Bus and virtual signals use the same four types; the Medium column says how they arrive. |
| Medium | Hardwired | Hardwired (a cable to the card; tested at the terminals), Bus (Profinet, IO-Link, Modbus…; tested at the device) or Virtual (computed by the controller; tested on the HMI). Empty = Hardwired. |
| Field tag | — | Only when the tag marked in the field differs from the I/O tag. |
| Rack | 0 | Controller rack / chassis. |
| Slot | 3 | Card slot. |
| Channel | 0 | Channel on the card. |
| PLC address | %IW64 | The address as the PLC writes it (%IW64, I:1/3…), or the device's bus address. |
| Signal | 4-20 mA | The electrical signal or protocol: 4-20 mA, 24 VDC, NAMUR, Profinet… |
| Signal low | 4 | Hardwired analogue only: low end of the electrical span (4). |
| Signal high | 20 | Hardwired analogue only: high end of the electrical span (20). |
| Signal unit | mA | mA, V… |
| Range low | 0 | Analogue (any medium): engineering range low (0). |
| Range high | 2 | Engineering range high (2). |
| Engineering unit | bar g | bar g, °C, L/min… as shown on the HMI. |
| Fail-safe state | Fail low | Digital: De-energized, Energized, Fail open, Fail closed, Fail last state. Analogue: Fail low, Fail high, Fail last value. |
| Device brand | Endress+Hauser | Instrument or actuator manufacturer (optional). |
| Device model | Cerabar PMP51 | Model (optional). Brand and model together make one catalogue entry. |
| Serial number | — | Serial of the installed unit (optional). |
| Notes | Headspace, top nozzle | Anything else: location, cable, remarks. |
Type and medium
The type says what the signal is and how it is tested: two states, or points along a span.
- DI
- Digital input — a contact, a proximity switch, a level switch.
- DO
- Digital output — a valve solenoid, a motor start, a lamp.
- AI
- Analogue input — a transmitter: 4–20 mA, 0–10 V, Pt100.
- AO
- Analogue output — a control valve positioner, a drive speed reference.
The medium says how it reaches the controller and so where it is tested. Together they make the class MGTrace shows: AI for a hardwired analogue input, NAI for the same value over a bus, VDI for a calculated flag.
- Hardwired
- A cable to the card. Tested at the terminals with a calibrator or a multimeter.
- Bus
- Profinet, IO-Link, Modbus, Ethernet/IP… Tested at the device, or by forcing it there.
- Virtual
- Computed by the controller. Tested on the HMI from the inputs that feed it.
Two ranges, not one
A pressure transmitter sends 4–20 mA and means 0–2 bar g. The loop check injects the first and reads the second, at 0, 50 and 100 % of span — so the template keeps Signal low / high / unit apart from Range low / high / Engineering unit. A list that mixes them is the usual reason a loop check is "done" and the HMI still reads wrong.
From the list to signed loop checks
Import the filled template into a project, trace each signal to the design element that specifies it, generate the loop checks per signal, execute them from a phone in the cabinet room and sign. Free for the first users, no time limit.